{"id":"CVE-2010-5305","published":"2019-03-26T17:24:25Z","modified":"2025-06-26T17:05:54Z","title":"Rockwell PLC5/SLC5/0x/RSLogix Credentials management","vendor":"Rockwell Automation","product":"PLC5","tier":"tail","description":{"text":"The potential exists for exposure of the product's password used to restrict unauthorized access to Rockwell PLC5/SLC5/0x/RSLogix 1785-Lx and 1747-L5x controllers. The potential exists for an unauthorized programming and configuration client to gain access to the product and allow changes to the product’s configuration or program. When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services.","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.05695,"percentile":0.9319,"provenance":"source"},"cwes":[{"id":"CWE-255","name":"Credentials management CWE-255"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-10-070-02","tags":["x_refsource_MISC"]},{"url":"http://rockwellautomation.custhelp.com/app/answers/detail/a_id/66684/kw/vulnerability/r_id/115100","tags":[]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-10-070-02","tags":["x_refsource_MISC","x_transferred"]}],"priority":{"score":18.6,"factors":[{"name":"EPSS percentile","points":18.64}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"PLC5","versions":["1785-Lx","1747-L5x"]},{"vendor":"Rockwell Automation","product":"SLC5/0x","versions":["1785-Lx","1747-L5x"]}],"workarounds":{"items":["To help reduce the likelihood of exploitation and associated security risk, Rockwell Automation recommends the following immediate mitigation strategies (Note: multiple strategies are recommended to be employed simultaneously): * For PLC-5 controllers, enable and configure \"Passwords and Privileges\" via RSLogix 5 configuration software to restrict access to critical data and improve overall password security. * When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services. This functionality can be enabled via RSLogix 5 or RSLogix 500 software. (Consult Rockwell TechnoteRockwell Technote, http://rockwellautomation.custhelp.com/app/answers/detail/a_id/66678/kw/vulnerability/r_id/115100 , website last accessed January 12, 2010 for applicable firmware versions) * Use the latest version of RSLogix 5 or RSLogix 500 configuration software and enable FactoryTalk Security services. * Disable where possible the capability to perform remote programming and configuration of the product over a network to a controller by placing the controller's key switch into RUN mode. * For SLC…"],"from":"CVE.org CNA","provenance":"source"},"summary":{"text":"The flaw is in the credentials management of Rockwell Automation's PLC5, SLC5/0x and RSLogix products, affecting 1785-Lx and 1747-L5x controllers, where the password that restricts unauthorized access can be exposed.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T21:04:37Z"},"euvd":{"id":"EUVD-2010-5264","exploited":false,"provenance":"source"}}