{"id":"CVE-2012-6437","published":"2013-01-24T21:00:00Z","modified":"2026-06-03T13:39:31Z","title":"Rockwell Automation ControlLogix PLC Improper Authentication","vendor":"Rockwell Automation","product":"1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules","tier":"tail","description":{"text":"The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause loss of availability, integrity, and confidentiality and a disruption in communications with other connected devices.\n\n\n\n\n\nRockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400","provenance":"source","from":"CVE.org"},"cvss":{"score":10,"severity":"CRITICAL","version":"2.0","vector":"AV:N/AC:L/Au:N/C:C/I:C/A:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.10532,"percentile":0.95881,"provenance":"source"},"cwes":[{"id":"CWE-287","name":"Improper Authentication"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03","tags":[]},{"url":"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154","tags":[]},{"url":"https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155","tags":[]},{"url":"https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156","tags":[]},{"url":"http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102","tags":[]},{"url":"http://www.us-cert.gov/control_systems/pdf/ICSA-13-011-03.pdf","tags":["x_refsource_MISC","x_transferred"]}],"priority":{"score":26.2,"factors":[{"name":"EPSS percentile","points":19.18},{"name":"CVSS severity","points":7.0}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules","versions":["All"]},{"vendor":"Rockwell Automation","product":"CompactLogix L32E and L35E controllers","versions":["All"]},{"vendor":"Rockwell Automation","product":"1788-ENBT FLEXLogix adapter","versions":["All"]},{"vendor":"Rockwell Automation","product":"1794-AENTR FLEX I/O EtherNet/IP adapter","versions":["All"]},{"vendor":"Rockwell Automation","product":"ControlLogix, CompactLogix, GuardLogix, and SoftLogix","versions":["<= 18"]},{"vendor":"Rockwell Automation","product":"CompactLogix and SoftLogix controllers","versions":["<= 19"]},{"vendor":"Rockwell Automation","product":"ControlLogix and GuardLogix controllers","versions":["<= 20"]},{"vendor":"Rockwell Automation","product":"MicroLogix","versions":["1100","1400"]}],"solutions":{"items":["According to Rockwell, any of the above products that become affected by a vulnerability can be reset by rebooting or power cycling the affected product. After the reboot, the affected product may require some reconfiguration. To mitigate the vulnerabilities, Rockwell has developed and released security patches on July 18, 2012, to address each of the issues. To download and install the patches please refer to Rockwell’s Advisories at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156 For more information on security with Rockwell Automation products, please refer to Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102 ."],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products. To mitigate the vulnerability with the Web server password authentication mechanism: * Upgrade the MicroLogix 1400 firmware to FRN 12 or higher. * Because of limitations in the MicroLogix 1100 platform, none of the firmware updates will be able to fix this issue, so users should use the following techniques to help reduce the likelihood of compromise. * Where possible, disable the Web server and change all default Administrator and Guest passwords. * If Web server functionality is needed, then Rockwell recommends upgrading the product’s firmware to the most current version to have the newest enhanced protections available such as: * When a controller receives two consecutive invalid authentication requests from an HTTP client, the controller resets the Authentication Counter after 60 minutes. * When a controller receives 10 invalid authentication requests from any HTTP client, it will not accept any valid or invalid authentication packets until a 24-hour…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2026-06-03T13:39:03.654457Z","from":"CISA ADP","provenance":"source"},"summary":{"text":"The flaw is improper authentication in the communication modules 1756-ENBT, 1756-EWEB, 1768-ENBT and 1768-EWEB from Rockwell Automation, where the device does not properly verify users before accepting firmware updates. A remote user with network access and no authentication can upload a new firmware image to the Ethernet card, whether corrupt or legitimate, which can compromise confidentiality, integrity and availability and disrupt communications with other connected devices.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:31:18Z"},"euvd":{"id":"EUVD-2012-6290","exploited":false,"provenance":"source"}}