{"id":"CVE-2013-2807","published":"2019-03-26T16:35:16Z","modified":"2024-08-06T15:52:20Z","title":"Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4…","vendor":"Rockwell Automation","product":"RSLinx Enterprise Software","tier":"tail","description":{"text":"Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.03855,"percentile":0.90412,"provenance":"source"},"cwes":[{"id":"CWE-190","name":"Integer Overflow or Wraparound"}],"references":[{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02","tags":["x_refsource_MISC"]}],"priority":{"score":18.1,"factors":[{"name":"EPSS percentile","points":18.08}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"RSLinx Enterprise Software","versions":["CPR9","CPR9-SR1","CPR9-SR2","CPR9-SR3","CPR9-SR4","CPR9-SR5","CPR9-SR5.1","CPR9-SR6"]}],"summary":{"text":"Rockwell Automation's RSLinx Enterprise Software, specifically the LogReceiver.exe component across CPR9 through CPR9-SR6, mishandles input when calculating the \"Total Record Size\" field. This logic error stems from an integer overflow or wraparound condition. An attacker who can send a crafted UDP datagram to port 4444 can set the \"Record Data Size\" field to an oversized value, causing an out-of-bounds read that crashes the service, which then requires a manual reboot to recover.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T21:25:01Z"},"euvd":{"id":"EUVD-2013-2746","exploited":false,"provenance":"source"}}