{"id":"CVE-2014-5410","published":"2014-10-03T18:00:00Z","modified":"2025-11-04T22:30:19Z","title":"Rockwell Automation Micrologix 1400 Improper Input Validation","vendor":"Rockwell Automation","product":"Allen-Bradley MicroLogix 1400","tier":"tail","description":{"text":"The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.1,"severity":"HIGH","version":"2.0","vector":"AV:N/AC:M/Au:N/C:N/I:N/A:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.04171,"percentile":0.91135,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295","tags":[]},{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-14-254-02","tags":[]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2014/icsa-14-254-02.json","tags":[]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02","tags":["x_refsource_MISC","x_transferred"]}],"priority":{"score":23.2,"factors":[{"name":"EPSS percentile","points":18.23},{"name":"CVSS severity","points":4.97}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"Allen-Bradley MicroLogix 1400","versions":["<= 1766-Lxxxxx Series A FRN 7","<= 1766-Lxxxxx Series B FRN 15.000"]}],"fixedVersions":[{"vendor":"Rockwell Automation","product":"Allen-Bradley MicroLogix 1400","versions":["Series B FRN 15.001 or higher"]}],"solutions":{"items":["Rockwell Automation has released a new version of MicroLogix 1400 Series B firmware to address the vulnerability and reduce associated risk to successful exploitation. Subsequent versions of MicroLogix 1400 Series B firmware and newer will incorporate these same enhancements. Rockwell Automation recommends the following immediate mitigation strategies (when possible, multiple strategies should be employed simultaneously): * Upgrade all MicroLogix 1400 Series B controllers to Series B FRN 15.001 or higher. Current firmware for the MicroLogix 1400 Series B platform can be obtained at the following web address: http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page Please refer to Rockwell Automation’s product disclosure (AID 620295) for more information on this topic available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["Users with Series A and Series B controllers are also recommended to apply the following risk mitigations: * Do not enable DNP3 communication in the product unless required. * Where appropriate, prohibit DNP3 communication that originates outside the perimeter of the manufacturing zone from entry into the zone by blocking communication directed at Ethernet communication Port 20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a firewall, UTM devices, or other security appliance) *Note: Ports 20000/TCP and 20000/UDP are factory defaults as per the DNP3 specification but can be reconfigured by the product owner. * Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked. * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment. * Employ layered security, defense-in-depth methods and network segregation and segmentation practices in system design to restrict and control access to…"],"from":"CVE.org CNA","provenance":"source"},"summary":{"text":"The DNP3 feature of Rockwell Automation Allen-Bradley MicroLogix 1400 controllers (1766-Lxxxxx A FRN 7 and earlier, and 1766-Lxxxxx B FRN before 15.001) mishandles input validation. An attacker with remote network access over either Ethernet or a serial line can send malformed packets to cause a denial of service that disrupts the controller's process, with no authentication or user interaction required.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:40:28Z"},"euvd":{"id":"EUVD-2014-5298","exploited":false,"provenance":"source"}}