{"id":"CVE-2014-9198","published":"2015-01-27T11:00:00Z","modified":"2025-09-05T21:18:01Z","title":"Schneider Electric ETG3000 FactoryCast HMI Gateway Use of Hard-coded Credentials","vendor":"Schneider Electric","product":"ETG3000 FactoryCast HMI Gateway","tier":"tail","description":{"text":"The FTP server on the Schneider Electric ETG3000 FactoryCast HMI Gateway with firmware through 1.60 IR 04 has hardcoded credentials, which makes it easier for remote attackers to obtain access via an FTP session.","provenance":"source","from":"CVE.org"},"cvss":{"score":10,"severity":"CRITICAL","version":"2.0","vector":"AV:N/AC:L/Au:N/C:C/I:C/A:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.04193,"percentile":0.91175,"provenance":"source"},"cwes":[{"id":"CWE-798","name":"Use of Hard-coded Credentials"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-15-020-02","tags":[]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-15-020-02","tags":["x_refsource_MISC","x_transferred"]},{"url":"http://www.securityfocus.com/bid/72258","tags":["vdb-entry","x_refsource_BID","x_transferred"]},{"url":"http://www.securityfocus.com/bid/77765","tags":["vdb-entry","x_refsource_BID","x_transferred"]}],"priority":{"score":25.2,"factors":[{"name":"EPSS percentile","points":18.23},{"name":"CVSS severity","points":7.0}]},"vendorSlug":"schneider-electric","affectedVersions":[{"vendor":"Schneider Electric","product":"ETG3000 FactoryCast HMI Gateway","versions":["TSXETG3000","TSXETG3010","TSXETG3021","TSXETG3022"]}],"solutions":{"items":["Schneider Electric has produced an updated firmware, labelled V1.60 IR 04. This firmware release moves the jar files directory in a secure area. The new firmware also includes the ability to disable the FTP server. This updated firmware can be downloaded at: http://www.schneider-electric.com/download/WW/EN/details/681790255-TSXETG30xx-V160-IR4/?showAsIframe... http://www.schneider-electric.com/download/WW/EN/details/681790255-TSXETG30xx-V160-IR4/"],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["Schneider Electric recommends the FTP server be deactivated when not needed. The firmware update does not remove the hard-coded credentials. Narendra Shinde also found that configuration files were accessible using default credentials. Schneider Electric recommends users change the default login credentials. This will protect configuration files from unauthorized access."],"from":"CVE.org CNA","provenance":"source"},"summary":{"text":"The FTP server in the Schneider Electric ETG3000 FactoryCast HMI Gateway, in firmware through 1.60 IR 04, contains hard-coded credentials. A remote attacker who can reach the FTP service over the network can use those built-in credentials to establish an FTP session and gain access, without needing prior authentication or user interaction.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:32:50Z"},"euvd":{"id":"EUVD-2014-9023","exploited":false,"provenance":"source"}}