{"id":"CVE-2017-14465","published":"2018-04-05T21:00:00Z","modified":"2024-09-16T23:46:47Z","title":"An exploitable access control vulnerability exists in the data, program, and function file permissions functionality…","vendor":"Talos","product":"Allen Bradley","tier":"tail","description":{"text":"An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Any input or output can be forced, causing unpredictable activity from the PLC.","provenance":"source","from":"CVE.org"},"cvss":{"score":10,"severity":"CRITICAL","version":"3.0","vector":"CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.35236,"percentile":0.9848,"provenance":"source"},"cwes":[],"references":[{"url":"https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443","tags":["x_refsource_MISC"]}],"priority":{"score":26.7,"factors":[{"name":"EPSS percentile","points":19.7},{"name":"CVSS severity","points":7.0}]},"vendorSlug":"talos","affectedVersions":[{"vendor":"Talos","product":"Allen Bradley","versions":["Allen Bradley Micrologix 1400 Series B FRN 21.2, Allen Bradley Micrologix 1400 Series B FRN 21.0, Allen Bradley Micrologix 1400 Series B FRN 15"]}],"summary":{"text":"An access control flaw in the data, program, and function file permissions functionality of the Allen Bradley Micrologix 1400 Series B controller, firmware FRN 21.2 and earlier, allows a crafted packet to perform read or write operations on the device. An attacker can exploit it remotely by sending unauthenticated packets while the keyswitch is in the REMOTE state, enabling disclosure of sensitive information, modification of settings or ladder logic, and forcing of any input or output, which can cause unpredictable PLC behaviour.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:29:49Z"},"euvd":{"id":"EUVD-2017-5968","exploited":false,"provenance":"source"}}