{"id":"CVE-2017-6030","published":"2017-06-30T02:35:00Z","modified":"2026-06-04T21:40:02Z","title":"Schneider Electric Modicon PLCs Predictable Value Range from Previous Values","vendor":"Schneider Electric","product":"Modicon M221","tier":"tail","description":{"text":"A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.","provenance":"source","from":"CVE.org"},"cvss":{"score":6.5,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L","provenance":"source","from":"CISA ADP Vulnrichment"},"epss":{"score":0.02184,"percentile":0.82827,"provenance":"source"},"cwes":[{"id":"CWE-343","name":"Predictable Value Range from Previous Values"}],"references":[{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02","tags":["x_refsource_MISC"]},{"url":"http://www.securityfocus.com/bid/97254","tags":["vdb-entry","x_refsource_BID"]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2017/icsa-17-089-02.json","tags":[]}],"priority":{"score":21.1,"factors":[{"name":"EPSS percentile","points":16.57},{"name":"CVSS severity","points":4.55}]},"vendorSlug":"schneider-electric","affectedVersions":[{"vendor":"Schneider Electric","product":"Modicon M221","versions":["< 1.5.0.0"]},{"vendor":"Schneider Electric","product":"Modicon M241","versions":["< 4.0.5.11"]},{"vendor":"Schneider Electric","product":"Modicon M251","versions":["< 4.0.5.11"]}],"solutions":{"items":["Schneider Electric has released new firmware versions to address the predictable value range from previous values vulnerability and the use of insufficiently random values vulnerability, which are available through Schneider Electric’s software update tool, SoMachine, Version 4.2, and SoMachineBasic, Version 1.5. Schneider Electric has not released a product to address the insufficiently protected credentials vulnerability; however, Schneider Electric has provided compensating controls to reduce the risk of exploitation. SoMachineBasic, Version 1.5, is available at the following location: http://www.schneider-electric.fr/fr/download/document/SOMBASAP15SOFT/ Schneider Electric has provided the following compensating controls to reduce the risk of exploitation of the insufficiently protected credentials vulnerability: * Verify that the hardware and software infrastructure that the PLCs are integrated into (along with all organizational measures and rules covering access to the infrastructure) consider the results of the hazard and risk analysis, and are implemented according to best practices and standards such as ISA/IEC 62443. * Limit traffic on the local network with managed…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2026-05-29T13:20:18.684514Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2017-15098","exploited":false,"provenance":"source"}}