{"id":"CVE-2017-6034","published":"2017-06-30T02:35:00Z","modified":"2026-06-04T21:07:21Z","title":"Schneider Electric Modicon Modbus Protocol Authentication Bypass by Capture-replay","vendor":"Schneider Electric","product":"Modicon Modbus Protocol","tier":"tail","description":{"text":"An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.","provenance":"source","from":"CVE.org"},"cvss":{"score":9.8,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CISA ADP Vulnrichment"},"epss":{"score":0.056,"percentile":0.93091,"provenance":"source"},"cwes":[{"id":"CWE-294","name":"Authentication Bypass by Capture-replay"}],"references":[{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-17-101-01","tags":[]},{"url":"http://www.securityfocus.com/bid/97562","tags":["vdb-entry","x_refsource_BID"]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2017/icsa-17-101-01.json","tags":[]},{"url":"https://www.se.com/us/en/download/document/SEVD-2017-065-01/","tags":[]}],"priority":{"score":25.5,"factors":[{"name":"EPSS percentile","points":18.62},{"name":"CVSS severity","points":6.86}]},"vendorSlug":"schneider-electric","affectedVersions":[{"vendor":"Schneider Electric","product":"Modicon Modbus Protocol","versions":["all versions"]}],"workarounds":{"items":["Schneider Electric has reported that they have introduced compensating controls to limit the exploitability of the identified vulnerabilities in many of the PLCs in the Modicon family; however, Schneider Electric recommends that users apply security measures to improve resiliency. Schneider Electric’s Momentum M1E controllers (all versions of model 171CBU98090 and all versions of model 171CBU98091) do not have built-in compensating controls to limit the exploitability of the identified vulnerabilities and Schneider Electric instructs users to take the following defensive measures: * Protect access to M1E controllers by a firewall blocking all remote/external access to Port 502. Schneider Electric reports that Modicon M340, M580, Premium and Quantum users should take one or more of the following defensive measures: * Enable protection based on an authentication to connect to PLC. This method relies on a feature named Application Password. Once enabled, password-based authentication is required whenever a user connects to change their application program; * Enable protection relying on an input (M340, Premium, Quantum) or a key switch in the front panel (Quantum) to reject remote…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2026-05-28T19:09:00.802921Z","from":"CISA ADP","provenance":"source"},"summary":{"text":"The Modicon Modbus Protocol from Schneider Electric contains an authentication bypass by capture-replay flaw, caused by sensitive information being transmitted in cleartext within the protocol. An attacker with network access can capture and replay run, stop, upload, and download commands, requiring no authentication or user interaction.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:32:35Z"},"euvd":{"id":"EUVD-2017-15102","exploited":false,"provenance":"source"}}