{"id":"CVE-2018-13815","published":"2018-12-13T16:00:00Z","modified":"2024-08-05T09:14:47Z","title":"A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6)","vendor":"Siemens","product":"SIMATIC S7-1200, SIMATIC S7-1500","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.01799,"percentile":0.78328,"provenance":"source"},"cwes":[{"id":"CWE-410","name":"Insufficient Resource Pool"}],"references":[{"url":"http://www.securityfocus.com/bid/105928","tags":["vdb-entry","x_refsource_BID"]},{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdf","tags":["x_refsource_CONFIRM"]}],"priority":{"score":15.7,"factors":[{"name":"EPSS percentile","points":15.67}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens AG","product":"SIMATIC S7-1200, SIMATIC S7-1500","versions":["SIMATIC S7-1200 : All versions","SIMATIC S7-1500 : All Versions < V2.6"]}],"euvd":{"id":"EUVD-2018-5751","exploited":false,"provenance":"source"}}