{"id":"CVE-2019-13524","published":"2020-01-16T17:53:12Z","modified":"2024-08-04T23:57:39Z","title":"GE PACSystems RX3i CPE100/115: All versions prior to R9.85,CPE302/305/310/330/400/410: All versions prior to…","vendor":null,"product":null,"tier":"tail","description":{"text":"GE PACSystems RX3i CPE100/115: All versions prior to R9.85,CPE302/305/310/330/400/410: All versions prior to R9.90,CRU/320 All versions(End of Life) may allow an attacker sending specially manipulated packets to cause the module state to change to halt-mode, resulting in a denial-of-service condition. An operator must reboot the CPU module after removing battery or energy pack to recover from halt-mode.","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.01549,"percentile":0.74888,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://www.us-cert.gov/ics/advisories/icsa-20-014-01","tags":["x_refsource_MISC"]}],"priority":{"score":15.0,"factors":[{"name":"EPSS percentile","points":14.98}]},"affectedVersions":[{"vendor":"n/a","product":"GE PACSystems RX3i","versions":["CPE100/115: All versions prior to R9.85,CPE302/305/310/330/400/410: All versions prior to R9.90,CRU320 All versions(End of Life)"]}],"euvd":{"id":"EUVD-2019-4979","exploited":false,"provenance":"source"}}