{"id":"CVE-2020-15787","published":"2020-09-09T18:11:40Z","modified":"2024-08-04T13:22:30Z","title":"A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16)","vendor":"Siemens","product":"SIMATIC HMI Unified Comfort Panels","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.01477,"percentile":0.7368,"provenance":"source"},"cwes":[{"id":"CWE-305","name":"Authentication Bypass by Primary Weakness"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-542525.pdf","tags":["x_refsource_MISC"]}],"priority":{"score":14.7,"factors":[{"name":"EPSS percentile","points":14.74}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC HMI Unified Comfort Panels","versions":["All versions <= V16"]}],"euvd":{"id":"EUVD-2020-7770","exploited":false,"provenance":"source"}}