{"id":"CVE-2021-23281","published":"2021-04-13T18:03:54Z","modified":"2024-09-17T02:41:57Z","title":"Remote Code execution","vendor":"Eaton","product":"Intelligent Power manager (IPM)","tier":"tail","description":{"text":"Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to unauthenticated remote code execution vulnerability. IPM software does not sanitize the date provided via coverterCheckList action in meta_driver_srv.js class. Attackers can send a specially crafted packet to make IPM connect to rouge SNMP server and execute attacker-controlled code.","provenance":"source","from":"CVE.org"},"cvss":{"score":10,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.02314,"percentile":0.83829,"provenance":"source"},"cwes":[{"id":"CWE-94","name":"Improper Control of Generation of Code"}],"references":[{"url":"https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf","tags":["x_refsource_MISC"]}],"priority":{"score":23.8,"factors":[{"name":"EPSS percentile","points":16.77},{"name":"CVSS severity","points":7.0}]},"vendorSlug":"eaton","affectedVersions":[{"vendor":"Eaton","product":"Intelligent Power manager (IPM)","versions":[">= unspecified, < 1.69"]}],"solutions":{"items":["upgrade the software to latest version 1.69"],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking ports 4679 & 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used"],"from":"CVE.org CNA","provenance":"source"},"euvd":{"id":"EUVD-2021-10376","exploited":false,"provenance":"source"}}