{"id":"CVE-2021-35533","published":"2021-11-26T16:37:27Z","modified":"2024-09-16T21:02:16Z","title":"Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series","vendor":"Hitachi Energy","product":"RTU500 series","tier":"tail","description":{"text":"Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.0095,"percentile":0.62112,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch","tags":["x_refsource_CONFIRM"]}],"priority":{"score":17.7,"factors":[{"name":"EPSS percentile","points":12.42},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"hitachi-energy","affectedVersions":[{"vendor":"Hitachi Energy","product":"RTU500 series","versions":[">= CMU Firmware version 12.0, <= 12.0.*",">= CMU Firmware version 12.2, <= 12.2.*",">= CMU Firmware version 12.4, <= 12.4.*"]}],"solutions":{"items":["- Disable BCI IEC 60870-5-104 function by configuration if it is not used. - Update to RTU500 series CMU Firmware version 12.6.5.0 or later (e.g., RTU500 CMU Firmware version 12.7.* or CMU Firmware version 13.2.* or later)."],"from":"CVE.org CNA","provenance":"source"},"euvd":{"id":"EUVD-2021-22169","exploited":false,"provenance":"source"}}