{"id":"CVE-2021-37205","published":"2022-02-09T15:16:57Z","modified":"2025-04-18T18:29:47Z","title":"A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET…","vendor":"Siemens","product":"SIMATIC Drive Controller family","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.0164,"percentile":0.76974,"provenance":"source"},"cwes":[{"id":"CWE-401","name":"Missing Release of Memory after Effective Lifetime"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-838121.pdf","tags":[]}],"priority":{"score":20.6,"factors":[{"name":"EPSS percentile","points":15.39},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC Drive Controller family","versions":["All versions >= V2.9.2 < V2.9.4"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)","versions":["All versions >= V21.9 < V21.9.4"]},{"vendor":"Siemens","product":"SIMATIC S7-1200 CPU family (incl. SIPLUS variants)","versions":["All versions >= V4.5.0 < V4.5.2"]},{"vendor":"Siemens","product":"SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)","versions":["All versions >= V2.9.2 < V2.9.4"]},{"vendor":"Siemens","product":"SIMATIC S7-1500 Software Controller","versions":["All versions >= V21.9 < V21.9.4"]},{"vendor":"Siemens","product":"SIMATIC S7-PLCSIM Advanced","versions":["All versions >= V4.0 < V4.0 SP1"]},{"vendor":"Siemens","product":"SIPLUS TIM 1531 IRC","versions":["All versions < V2.3.6"]},{"vendor":"Siemens","product":"TIM 1531 IRC","versions":["All versions < V2.3.6"]}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-04-18T15:12:33.320440Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2021-23779","exploited":false,"provenance":"source"}}