{"id":"CVE-2021-42534","published":"2021-10-22T13:17:15Z","modified":"2024-09-16T23:52:08Z","title":"Trane Building Automation Controllers Cross-site Scripting","vendor":"Trane","product":"Tracer SC","tier":"tail","description":{"text":"The affected product’s web application does not properly neutralize the input during webpage generation, which could allow an attacker to inject code in the input forms.","provenance":"source","from":"CVE.org"},"cvss":{"score":6.3,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00607,"percentile":0.49981,"provenance":"source"},"cwes":[{"id":"CWE-79","name":"Improper Neutralization of Input During Web Page Generation"}],"references":[{"url":"https://us-cert.cisa.gov/ics/advisories/icsa-21-292-02","tags":["x_refsource_CONFIRM"]}],"priority":{"score":14.4,"factors":[{"name":"EPSS percentile","points":10.0},{"name":"CVSS severity","points":4.41}]},"vendorSlug":"trane","affectedVersions":[{"vendor":"Trane","product":"Tracer SC","versions":[">= All, <= 3.8"]}],"solutions":{"items":["Trane has identified the following specific mitigations for the affected products: Users upgrade Tracer SC controllers running firmware v3.8 and prior, to firmware v4.4 SP7 or higher. Users should contact a regional Trane office to install updated firmware or request additional information and reference Trane service database number HUB-207592. Tracer SC is no longer actively developed, tested, or sold. Tracer SC will be considered end-of-life on December 31, 2022. Trane recommends users identify a migration plan to replace the Tracer SC controller with the Tracer SC+ controller, which can function as a drop-in replacement for Tracer SC, providing significant security upgrades."],"from":"CVE.org CNA","provenance":"source"},"euvd":{"id":"EUVD-2021-29503","exploited":false,"provenance":"source"}}