{"id":"CVE-2022-29492","published":"2022-09-14T17:07:31Z","modified":"2025-06-04T15:03:09Z","title":"A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP…","vendor":"Hitachi Energy","product":"MicroSCADA X SYS600","tier":"tail","description":{"text":"Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*","provenance":"source","from":"CVE.org"},"cvss":{"score":5.3,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00762,"percentile":0.56251,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch","tags":["x_refsource_CONFIRM"]}],"priority":{"score":15.0,"factors":[{"name":"EPSS percentile","points":11.25},{"name":"CVSS severity","points":3.71}]},"vendorSlug":"hitachi-energy","affectedVersions":[{"vendor":"Hitachi Energy","product":"MicroSCADA X SYS600","versions":["10","10.1","10.1.1","10.2","10.2.1","10.3","10.3.1"]},{"vendor":"Hitachi Energy","product":"MicroSCADA Pro SYS600","versions":[">= unspecified, <= 9.2 FP2 Hotfix 4"]}],"solutions":{"items":["Remediated in SYS600 10.4 For MicroSCADA Pro SYS600 - Upgrade to at least SYS600 version 10.4. For MicroSCADA X SYS600 - Update to at least SYS600 version 10.4."],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["Apply general mitigation factors as specify in the advisory."],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-06-04T15:03:06.930475Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2022-33830","exploited":false,"provenance":"source"}}