{"id":"CVE-2022-30319","published":"2022-07-28T15:50:53Z","modified":"2024-11-20T16:16:57Z","title":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass","vendor":null,"product":null,"tier":"tail","description":{"text":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.","provenance":"source","from":"CVE.org"},"cvss":null,"epss":{"score":0.00704,"percentile":0.54234,"provenance":"source"},"cwes":[],"references":[{"url":"https://www.forescout.com/blog/","tags":["x_refsource_MISC"]},{"url":"https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03","tags":["x_refsource_MISC"]}],"priority":{"score":10.8,"factors":[{"name":"EPSS percentile","points":10.85}]},"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2024-11-20T16:16:14.742165Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2022-52707","exploited":false,"provenance":"source"}}