{"id":"CVE-2022-34820","published":"2022-07-12T10:07:29Z","modified":"2025-04-21T13:51:29Z","title":"A vulnerability has been identified in SIMATIC CP 1242-7 V2 (All versions < V3.3.46), SIMATIC CP 1243-1 (All versions…","vendor":"Siemens","product":"SIMATIC CP 1242-7 V2","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC CP 1242-7 V2 (All versions < V3.3.46), SIMATIC CP 1243-1 (All versions < V3.3.46), SIMATIC CP 1243-7 LTE EU (All versions < V3.3.46), SIMATIC CP 1243-7 LTE US (All versions < V3.3.46), SIMATIC CP 1243-8 IRC (All versions < V3.3.46), SIMATIC CP 1542SP-1 IRC (All versions >= V2.0 < V2.2.28), SIMATIC CP 1543-1 (All versions < V3.0.22), SIMATIC CP 1543SP-1 (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS NET CP 1242-7 V2 (All versions < V3.3.46), SIPLUS NET CP 1543-1 (All versions < V3.0.22), SIPLUS S7-1200 CP 1243-1 (All versions < V3.3.46), SIPLUS S7-1200 CP 1243-1 RAIL (All versions < V3.3.46). The application does not correctly escape some user provided fields during the authentication process. This could allow an attacker to inject custom commands and execute arbitrary code with elevated privileges.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.4,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.0227,"percentile":0.83482,"provenance":"source"},"cwes":[{"id":"CWE-77","name":"Improper Neutralization of Special Elements used in a Command"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-517377.pdf","tags":[]}],"priority":{"score":22.6,"factors":[{"name":"EPSS percentile","points":16.7},{"name":"CVSS severity","points":5.88}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC CP 1242-7 V2","versions":["All versions < V3.3.46"]},{"vendor":"Siemens","product":"SIMATIC CP 1243-1","versions":["All versions < V3.3.46"]},{"vendor":"Siemens","product":"SIMATIC CP 1243-7 LTE EU","versions":["All versions < V3.3.46"]},{"vendor":"Siemens","product":"SIMATIC CP 1243-7 LTE US","versions":["All versions < V3.3.46"]},{"vendor":"Siemens","product":"SIMATIC CP 1243-8 IRC","versions":["All versions < V3.3.46"]},{"vendor":"Siemens","product":"SIMATIC CP 1542SP-1 IRC","versions":["All versions >= V2.0 < V2.2.28"]},{"vendor":"Siemens","product":"SIMATIC CP 1543-1","versions":["All versions < V3.0.22"]},{"vendor":"Siemens","product":"SIMATIC CP 1543SP-1","versions":["All versions >= V2.0 < V2.2.28"]},{"vendor":"Siemens","product":"SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL","versions":["All versions >= V2.0 < V2.2.28"]},{"vendor":"Siemens","product":"SIPLUS ET 200SP CP 1543SP-1 ISEC","versions":["All versions >= V2.0 < V2.2.28"]}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2025-04-18T15:22:59.563603Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2022-37726","exploited":false,"provenance":"source"}}