{"id":"CVE-2022-45138","published":"2023-02-27T14:36:20Z","modified":"2025-03-10T17:20:50Z","title":"WAGO: Missing Authentication for Critical Function","vendor":"WAGO","product":"Compact Controller CC100 (751-9301)","tier":"tail","description":{"text":"The configuration backend of the web-based management can be used by unauthenticated users, although only authenticated users should be able to use the API. The vulnerability allows an unauthenticated attacker to read and set several device parameters that can lead to full compromise of the device.","provenance":"source","from":"CVE.org"},"cvss":{"score":9.8,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.0074,"percentile":0.55508,"provenance":"source"},"cwes":[{"id":"CWE-306","name":"Missing Authentication for Critical Functionality"}],"references":[{"url":"https://cert.vde.com/en/advisories/VDE-2022-060/","tags":[]}],"priority":{"score":18.0,"factors":[{"name":"EPSS percentile","points":11.1},{"name":"CVSS severity","points":6.86}]},"vendorSlug":"wago","affectedVersions":[{"vendor":"WAGO","product":"Compact Controller CC100 (751-9301)","versions":[">= FW16, < FW22","FW23"]},{"vendor":"WAGO","product":"Edge Controller (752-8303/8000-002)","versions":[">= FW18, < FW22","FW23"]},{"vendor":"WAGO","product":"PFC100 (750-81xx/xxx-xxx)","versions":[">= FW16, < FW22","FW23"]},{"vendor":"WAGO","product":"PFC200 (750-82xx/xxx-xxx)","versions":[">= FW16, < FW22","FW23"]},{"vendor":"WAGO","product":"Touch Panel 600 Advanced Line (762-5xxx)","versions":[">= FW16, < FW22","FW23"]},{"vendor":"WAGO","product":"Touch Panel 600 Marine Line (762-6xxx)","versions":[">= FW16, < FW22","FW23"]},{"vendor":"WAGO","product":"Touch Panel 600 Standard Line (762-4xxx)","versions":[">= FW16, < FW22","FW23"]}],"fixedVersions":[{"vendor":"WAGO","product":"Compact Controller CC100 (751-9301)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"Edge Controller (752-8303/8000-002)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"PFC100 (750-81xx/xxx-xxx)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"PFC200 (750-82xx/xxx-xxx)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"Touch Panel 600 Advanced Line (762-5xxx)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"Touch Panel 600 Marine Line (762-6xxx)","versions":["FW22 Patch 1"]},{"vendor":"WAGO","product":"Touch Panel 600 Standard Line (762-4xxx)","versions":["FW22 Patch 1"]}],"capec":[{"id":"CAPEC-115","name":"Authentication Bypass"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2025-03-10T17:20:33.215201Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2022-48053","exploited":false,"provenance":"source"}}