{"id":"CVE-2022-47374","published":"2023-12-12T11:25:31Z","modified":"2026-02-25T16:34:35Z","title":"A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All…","vendor":"Siemens","product":"SIMATIC PC-Station Plus","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly.\r\n\r\nThis could allow an attacker to exhaust system resources and create a denial of service condition for the device.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.0072,"percentile":0.54836,"provenance":"source"},"cwes":[{"id":"CWE-674","name":"Uncontrolled Recursion"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-892915.pdf","tags":[]}],"priority":{"score":16.2,"factors":[{"name":"EPSS percentile","points":10.97},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC PC-Station Plus","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC S7-400 CPU 412-2 PN V7","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC S7-400 CPU 414-3 PN/DP V7","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC S7-400 CPU 414F-3 PN/DP V7","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC S7-400 CPU 416-3 PN/DP V7","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC S7-400 CPU 416F-3 PN/DP V7","versions":["All versions"]},{"vendor":"Siemens","product":"SINAMICS S120 (incl. SIPLUS variants)","versions":["All versions < V5.2 SP3 HF15"]},{"vendor":"Siemens","product":"SIPLUS S7-400 CPU 414-3 PN/DP V7","versions":["All versions"]},{"vendor":"Siemens","product":"SIPLUS S7-400 CPU 416-3 PN/DP V7","versions":["All versions"]}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2023-12-23T05:01:16.237841Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2022-50141","exploited":false,"provenance":"source"}}