{"id":"CVE-2023-0053","published":"2023-03-02T00:15:49Z","modified":"2025-01-16T21:55:31Z","title":"SAUTER Controls Nova 200–220 Series Cleartext Transmission of Sensitive Information","vendor":"SAUTER Controls","product":"Nova 220 (EYK220F001) DDC with BACnet connection","tier":"tail","description":{"text":"SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and \nprior and BACnetstac version 4.2.1 and prior have only FTP and Telnet \navailable for device management. Any sensitive information communicated \nthrough these protocols, such as credentials, is sent in cleartext. An \nattacker could obtain sensitive information such as user credentials to \ngain access to the system. \n\n\n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00386,"percentile":0.33569,"provenance":"source"},"cwes":[{"id":"CWE-319","name":"Cleartext Transmission of Sensitive Information"}],"references":[{"url":"https://www.cisa.gov/uscert/ics/advisories/icsa-23-012-05","tags":[]}],"priority":{"score":12.0,"factors":[{"name":"EPSS percentile","points":6.71},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"sauter-controls","affectedVersions":[{"vendor":"SAUTER Controls","product":"Nova 220 (EYK220F001) DDC with BACnet connection","versions":[">= Firmware all versions, <= 3.3-006",">= BACnetstac all versions, <= 4.2.1"]},{"vendor":"SAUTER Controls","product":"Nova 230 (EYK230F001) DDC with BACnet connection","versions":[">= Firmware all versions, <= 3.3-006",">= BACnetstac all versions, <= 4.2.1"]},{"vendor":"SAUTER Controls","product":"Nova 106 (EYK300F001) BACnet communication card","versions":[">= Firmware all versions, <= 3.3-006",">= BACnetstac all versions, <= 4.2.1"]},{"vendor":"SAUTER Controls","product":"moduNet300 (EY-AM300F001, EY-AM300F002)","versions":[">= Firmware all versions, <= 3.3-006",">= BACnetstac all versions, <= 4.2.1"]}],"workarounds":{"items":["SAUTER Controls has stated that this product line is no longer supported, as it was discontinued in 2016. SAUTER Controls recommends users take all necessary measures to protect the integrity of building automation network access, using all appropriate means and policies to minimize risks. Sauter Controls recommends users evaluate and upgrade legacy systems to current solutions where necessary. Affected users should contact SAUTER Controls https://www.sauter-controls.com/  for instructions on upgrading legacy systems."],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-01-16T20:56:33.933472Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-12156","exploited":false,"provenance":"source"}}