{"id":"CVE-2023-0811","published":"2023-03-16T17:41:25Z","modified":"2025-01-16T21:42:32Z","title":"Omron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored","vendor":"Omron","product":"CJ1M SYSMAC CJ-series","tier":"tail","description":{"text":"\nOmron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an adversary issues a PROGRAM AREA WRITE command to a specific memory region, they could overwrite the password. This may lead to disabling UM protections or setting a non-ASCII password (non-keyboard characters) and preventing an engineer from viewing or modifying the user program. \n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":9.1,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00621,"percentile":0.50693,"provenance":"source"},"cwes":[{"id":"CWE-284","name":"Improper Access Control"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01","tags":[]},{"url":"https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf","tags":[]}],"priority":{"score":16.5,"factors":[{"name":"EPSS percentile","points":10.14},{"name":"CVSS severity","points":6.37}]},"vendorSlug":"omron","affectedVersions":[{"vendor":"Omron ","product":"CJ1M SYSMAC CJ-series","versions":["All versions"]},{"vendor":"Omron","product":"CJ1M SYSMAC CJ-series","versions":["All versions"]},{"vendor":"Omron","product":"CJ1M SYSMAC CJ-series","versions":["All versions"]},{"vendor":"Omron","product":"CJ1M SYSMAC CJ-series","versions":["All versions"]},{"vendor":"Omron ","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]},{"vendor":"Omron ","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]},{"vendor":"Omron ","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]},{"vendor":"Omron ","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]},{"vendor":"Omron","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]},{"vendor":"Omron ","product":"CJ1M SYSMAC CS-series ","versions":["All versions"]}],"workarounds":{"items":["OMRON has released the following countermeasures for users to implement: * Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit) * Set UM read protection password and “Prohibit from overwriting to a protected program “option. If the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures: Security measures to prevent unauthorized access: * If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures. * Enable the FINS write protection function. * Select the Protect by IP Address * Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them. * Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network. * Use a virtual private network (VPN) for remote access to control systems and equipment. * Use strong passwords and change them frequently. * Install physical controls so that only authorized personnel can access control systems…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-01-16T20:56:16.921497Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-12816","exploited":false,"provenance":"source"}}