{"id":"CVE-2023-1285","published":"2023-04-14T02:17:55Z","modified":"2025-02-06T20:57:38Z","title":"Signal Handler Race Condition vulnerability in Mitsubishi Electric India GC-ENET-COM whose first 2 digits of 11-digit…","vendor":"Mitsubishi Electric India","product":"GC-ENET-COM","tier":"tail","description":{"text":"Signal Handler Race Condition vulnerability in Mitsubishi Electric India GC-ENET-COM whose first 2 digits of 11-digit serial number of unit are \"16\" allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition in Ethernet communication by sending a large number of specially crafted packets to any UDP port when GC-ENET-COM is configured as a Modbus TCP Server. The communication resumes only when the power of the main unit is turned off and on or when the GC-ENET-COM is hot-swapped from the main unit.\n","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00686,"percentile":0.53553,"provenance":"source"},"cwes":[{"id":"CWE-364","name":"Signal Handler Race Condition"}],"references":[{"url":"https://mitsubishielectric.in/fa/cnc-pdf/DoS_in_Ethernet_Communication_Extension_Unit_GC_ENET_COM_of_GOC35_Series.pdf","tags":["vendor-advisory"]},{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-103-15","tags":["government-resource"]}],"priority":{"score":16.0,"factors":[{"name":"EPSS percentile","points":10.71},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"mitsubishi-electric-india","affectedVersions":[{"vendor":"Mitsubishi Electric India","product":"GC-ENET-COM","versions":["SN:16XXXXXXXXX"]}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-02-06T20:56:57.330519Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-23551","exploited":false,"provenance":"source"}}