{"id":"CVE-2023-22807","published":"2023-02-15T17:29:47Z","modified":"2025-01-16T21:56:14Z","title":"CVE-2023-22807","vendor":"LS Electric","product":"XBC-DN32U","tier":"tail","description":{"text":"LS ELECTRIC XBC-DN32U with operating system version 01.80 does not properly control access to the PLC over its internal XGT protocol.  An attacker could control and tamper with the PLC by sending the packets to the PLC over its XGT protocol.\n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":9.8,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00668,"percentile":0.52848,"provenance":"source"},"cwes":[{"id":"CWE-284","name":"Improper Access Control"}],"references":[{"url":"https://www.cisa.gov/uscert/ics/advisories/icsa-23-040-02","tags":[]}],"priority":{"score":17.4,"factors":[{"name":"EPSS percentile","points":10.57},{"name":"CVSS severity","points":6.86}]},"vendorSlug":"ls-electric","affectedVersions":[{"vendor":"LS Electric","product":"XBC-DN32U","versions":["Operating System Version 01.80"]}],"workarounds":{"items":["LS ELECTRIC is developing mitigations (to be released tentatively by the end of 2023) and recommends users follow the provided workarounds to reduce the risk of exploitation: * Restrict communication to the PLC to only trusted IP addresses and trusted devices by enabling the “Host Table” option in the configuration window of the PLC."],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2025-01-16T20:59:11.235636Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-26919","exploited":false,"provenance":"source"}}