{"id":"CVE-2023-29464","published":"2023-10-13T12:57:25Z","modified":"2024-09-17T16:58:55Z","title":"Rockwell Automation FactoryTalk Linx Vulnerable to Denial-of-Service and Information Disclosure","vendor":"Rockwell Automation","product":"FactoryTalk Linx ","tier":"tail","description":{"text":"\nFactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from memory via crafted malicious packets. Sending a size larger than the buffer size results in leakage of data from memory resulting in an information disclosure. If the size is large enough, it causes communications over the common industrial protocol to become unresponsive to any type of packet, resulting in a denial-of-service to FactoryTalk Linx over the common industrial protocol.\n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":8.2,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.14972,"percentile":0.96794,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1141040","tags":[]}],"priority":{"score":25.1,"factors":[{"name":"EPSS percentile","points":19.36},{"name":"CVSS severity","points":5.74}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"FactoryTalk Linx ","versions":["6.20","6.30"]}],"solutions":{"items":["* Install the security patches for the respective versions, referencing BF29637 - Patch: Hardening of the FactoryTalk Linx communications service for MobileView to authenticate and block improperly sized files, FactoryTalk Linx 6.20, 6.30 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140402 ."],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-10","name":"Buffer Overflow via Environment Variables"}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2024-09-17T16:57:57.383746Z","from":"CISA ADP","provenance":"source"},"summary":{"text":"FactoryTalk Linx, the component within Rockwell Automation's PanelView Plus, contains an improper input validation flaw in how it handles packets sent over the Common Industrial Protocol. An unauthenticated attacker on the network can send crafted packets with a size larger than the buffer, causing data to leak from memory and, if the size is large enough, leaving communications over the protocol unresponsive to any packet.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-20T06:34:51Z"},"euvd":{"id":"EUVD-2023-33033","exploited":false,"provenance":"source"}}