{"id":"CVE-2023-3321","published":"2023-07-24T17:06:31Z","modified":"2024-10-24T15:59:10Z","title":"Code Execution through Writable Mosquitto Configuration File","vendor":"ABB","product":"ABB Ability™ zenon","tier":"tail","description":{"text":"\nA vulnerability exists by allowing low-privileged users to read and update the data in various directories used by the Zenon system. An attacker could exploit the vulnerability by using specially crafted\nprograms to exploit the vulnerabilities by allowing them to run on the zenon installed hosts.\nThis issue affects ABB Ability™ zenon: from 11 build through 11 build 106404.\n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":7,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00366,"percentile":0.31219,"provenance":"source"},"cwes":[{"id":"CWE-15","name":"External Control of System or Configuration Setting"}],"references":[{"url":"https://search.abb.com/library/Download.aspx?DocumentID=2NGA001801&LanguageCode=en&DocumentPartId=&Action=Launch&_ga=2.194142766.2067879716.1690216773-1911411808.1686627590","tags":[]}],"priority":{"score":11.1,"factors":[{"name":"EPSS percentile","points":6.24},{"name":"CVSS severity","points":4.9}]},"vendorSlug":"abb","affectedVersions":[{"vendor":"ABB","product":"ABB Ability™ zenon","versions":[">= 11 build, <= 11 build 106404"]}],"workarounds":{"items":["ABB recommends the following workarounds. Although these workarounds will not correct the underlying vulnerability, they block the known attack vectors. • For CVE-2023-3321, Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed.  Remove the default directory permissions for ‘Everyone’ on the service grid, ABB utilities, and zenon_Projects directories and provide access only to specific users that are expected to access zenon.  Install the IIoT services, which is, the Service grid component on a separate system.  Secure the ZEE600 related executable files in ‘C:\\ProgramData\\ABB\\ABBUtilities’ directory by removing the group named “Everyone”.  Ensure the group name “Everyone” should be removed from the following directory. ‘C:\\ProgramData\\ABB’.  Secure zenon_Projects directory by managing the access permissions. The project directory should have access only for the user group (Excluding administrator) which has the users to use zenon projects. Consider the following example: Example: A user group…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2024-10-24T15:59:00.259510Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-43989","exploited":false,"provenance":"source"}}