{"id":"CVE-2023-51440","published":"2024-02-13T09:00:04Z","modified":"2024-08-02T22:32:10Z","title":"A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean…","vendor":"Siemens","product":"SIMATIC CP 343-1","tier":"tail","description":{"text":"A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK7343-1CX10-0XE0) (All versions), SIPLUS NET CP 343-1 (6AG1343-1EX30-7XE0) (All versions), SIPLUS NET CP 343-1 Lean (6AG1343-1CX10-2XE0) (All versions). Affected products incorrectly validate TCP sequence numbers. This could allow an unauthenticated remote attacker to create a denial of service condition by injecting spoofed TCP RST packets.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:T/RC:C","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00597,"percentile":0.49465,"provenance":"source"},"cwes":[{"id":"CWE-940","name":"Improper Verification of Source of a Communication Channel"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/html/ssa-516818.html","tags":[]}],"priority":{"score":15.1,"factors":[{"name":"EPSS percentile","points":9.89},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC CP 343-1","versions":["All versions"]},{"vendor":"Siemens","product":"SIMATIC CP 343-1 Lean","versions":["All versions"]},{"vendor":"Siemens","product":"SIPLUS NET CP 343-1","versions":["All versions"]},{"vendor":"Siemens","product":"SIPLUS NET CP 343-1 Lean","versions":["All versions"]}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2024-02-21T20:12:53.508055Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2023-56160","exploited":false,"provenance":"source"}}