{"id":"CVE-2024-3493","published":"2024-04-15T21:17:36Z","modified":"2024-08-12T15:16:08Z","title":"Rockwell Automation ControlLogix and GaurdLogix Vulnerable to Major Nonrecoverable Fault Due to Invalid Header Value","vendor":"Rockwell Automation","product":"ControlLogix 5580","tier":"tail","description":{"text":"\nA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \n\n","provenance":"source","from":"CVE.org"},"cvss":{"score":8.6,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00637,"percentile":0.51489,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html","tags":[]}],"priority":{"score":16.3,"factors":[{"name":"EPSS percentile","points":10.3},{"name":"CVSS severity","points":6.02}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"ControlLogix 5580","versions":["v35.011"]},{"vendor":"Rockwell Automation","product":"GuardLogix 5580","versions":["v35.011"]},{"vendor":"Rockwell Automation","product":"CompactLogix 5380","versions":["v5.001"]},{"vendor":"Rockwell Automation","product":"1756-EN4TR","versions":["v5.001"]}],"solutions":{"items":["Affected Product First Known in Firmware Revision Corrected in Firmware Revision ControlLogix® 5580 V35.011 V35.013, V36.011 GuardLogix 5580 V35.011 V35.013, V36.011 CompactLogix 5380 V35.011 V35.013, V36.011 1756-EN4TR V5.001 V6.001 Users using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-137","name":"Parameter Injection"}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2024-08-12T15:09:28.736089Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-32079","exploited":false,"provenance":"source"}}