{"id":"CVE-2024-37365","published":"2024-11-12T14:52:55Z","modified":"2024-11-12T19:04:00Z","title":"FactoryTalk View ME Remote Code Execution Vulnerability via Project Save Path","vendor":"Rockwell Automation","product":"FactoryTalk View Machine Edition","tier":"tail","description":{"text":"A remote code execution vulnerability exists in the affected\nproduct. The vulnerability allows users to save projects within the public\ndirectory allowing anyone with local access to modify and/or delete files. Additionally,\na malicious user could potentially leverage this vulnerability to escalate\ntheir privileges by changing the macro to execute arbitrary code.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.3,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00225,"percentile":0.13451,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1709.html","tags":[]}],"priority":{"score":7.8,"factors":[{"name":"EPSS percentile","points":2.69},{"name":"CVSS severity","points":5.11}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"FactoryTalk View Machine Edition","versions":[">=V14"]}],"solutions":{"items":["Upgrade to Version 15"],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["· To enhance security and prevent unauthorized modifications to HMI project files, harden the Windows OS by removing the INTERACTIVE group from the folder’s security properties. · Add specific users or user groups and assign their permissions to this folder using the least privileges principle. Users with read-only permission can still test run and run the FactoryTalk View ME Station. · Guidance can be found in FactoryTalk View ME v14 Help topic: “HMI projects folder settings”. It can be opened through FactoryTalk View ME Studio menu “help\\Contents\\FactoryTalk View ME Help\\Create a Machine Edition application->Open applications->HMI project folder settings”.  Security Best Practices"],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-242","name":"Code Injection"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2024-11-12T19:02:19.102188Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-36614","exploited":false,"provenance":"source"}}