{"id":"CVE-2024-3982","published":"2024-08-27T12:47:21Z","modified":"2024-08-27T17:52:18Z","title":"An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging…","vendor":"Hitachi Energy","product":"MicroSCADA SYS600","tier":"tail","description":{"text":"An attacker with local access to machine where MicroSCADA X\nSYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level\nis not enabled and only users with administrator rights can enable it.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.2,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00219,"percentile":0.1263,"provenance":"source"},"cwes":[{"id":"CWE-294","name":"Authentication Bypass by Capture-replay"}],"references":[{"url":"https://publisher.hitachienergy.com/preview?DocumentID=8DBD000160&LanguageCode=en&DocumentPartId=&Action=Launch","tags":[]}],"priority":{"score":8.3,"factors":[{"name":"EPSS percentile","points":2.53},{"name":"CVSS severity","points":5.74}]},"vendorSlug":"hitachi-energy","affectedVersions":[{"vendor":"Hitachi Energy","product":"MicroSCADA SYS600","versions":[">= 10.0, <= 10.5"]}],"capec":[{"id":"CAPEC-593","name":"Session Hijacking"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2024-08-27T17:49:48.661304Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-32548","exploited":false,"provenance":"source"}}