{"id":"CVE-2024-5800","published":"2024-08-10T03:50:02Z","modified":"2024-08-12T14:32:22Z","title":"Diffie-Hellman groups with insufficient strength used in SSL/TLS stack of B&R Automation Runtime","vendor":"B&R Industrial Automation","product":"Automation Runtime","tier":"tail","description":{"text":"Diffie-Hellman groups with insufficient strength are used in the SSL/TLS stack of B&R Automation Runtime versions before 6.0.2, allowing a network attacker to decrypt the SSL/TLS communication.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.3,"severity":"HIGH","version":"4.0","vector":"CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:L/VA:N/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00252,"percentile":0.17021,"provenance":"source"},"cwes":[{"id":"CWE-326","name":"Inadequate Encryption Strength"}],"references":[{"url":"https://www.br-automation.com/fileadmin/SA24P011-d8aaf02f.pdf","tags":[]}],"priority":{"score":9.2,"factors":[{"name":"EPSS percentile","points":3.4},{"name":"CVSS severity","points":5.81}]},"vendorSlug":"b-and-r-industrial-automation","affectedVersions":[{"vendor":"B&R Industrial Automation","product":"Automation Runtime","versions":["< 6.0.0"]}],"fixedVersions":[{"vendor":"B&R Industrial Automation","product":"Automation Runtime","versions":["6.0.2"]}],"capec":[{"id":"CAPEC-117","name":"Interception"},{"id":"CAPEC-148","name":"Content Spoofing"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2024-08-12T14:32:07.188310Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-46948","exploited":false,"provenance":"source"}}