{"id":"CVE-2024-6077","published":"2024-09-12T19:59:40Z","modified":"2024-09-12T21:01:50Z","title":"Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix® 5380 Vulnerable to DoS…","vendor":"Rockwell Automation","product":"CompactLogix 5380","tier":"tail","description":{"text":"A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.7,"severity":"HIGH","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00558,"percentile":0.47392,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1963.html","tags":[]}],"priority":{"score":15.6,"factors":[{"name":"EPSS percentile","points":9.48},{"name":"CVSS severity","points":6.09}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"CompactLogix 5380","versions":["v.32 .011"]},{"vendor":"Rockwell Automation","product":"CompactLogix 5380 Process","versions":["v.33.011"]},{"vendor":"Rockwell Automation","product":"Compact GuardLogix 5380 SIL 2","versions":["v.32.013"]},{"vendor":"Rockwell Automation","product":"Compact GuardLogix 5380 SIL 3","versions":["v.32.011"]},{"vendor":"Rockwell Automation","product":"CompactLogix 5480","versions":["v.32.011"]},{"vendor":"Rockwell Automation","product":"ControlLogix® 5580","versions":["v.32.011"]},{"vendor":"Rockwell Automation","product":"ControlLogix® 5580 Process","versions":["v.33.011"]},{"vendor":"Rockwell Automation","product":"GuardLogix 5580","versions":["v.32.011"]},{"vendor":"Rockwell Automation","product":"1756-EN4","versions":["v2.001"]}],"solutions":{"items":["Affected Family First Known in Software/Firmware Version Corrected in Software/Firmware Version CompactLogix 5380 v.32 .011 v33.017, v34.014, v35.013, v36.011 and later CompactLogix 5380 Process v.33.011 v33.017, v34.014, v35.013, v36.011 and later Compact GuardLogix 5380 SIL 2 v.32.013 v33.017, v34.014, v35.013, v36.011 and later Compact GuardLogix 5380 SIL 3 v.32.011 v33.017, v34.014, v35.013, v36.011 and later CompactLogix 5480 v.32.011 v33.017, v34.014, v35.013, v36.011 and later ControlLogix® 5580 v.32.011 v33.017, v34.014, v35.013, v36.011 and later ControlLogix® 5580 Process v.33.011 v33.017, v34.014, v35.013, v36.011 and later GuardLogix 5580 v.32.011 v33.017, v34.014, v35.013, v36.011 and later 1756-EN4 v2.001 v6.001 and later Mitigations and Workarounds Customers who are unable to upgrade to the corrected software versions are encouraged to apply the following risk mitigations. * Users who do not wish to use CIP security can disable the feature per device. See \"Disable CIP Security\" in Chapter 2 of \"CIP Security with Rockwell Automation Products\" (publication SECURE-AT001) For information on how to mitigate Security Risks on industrial automation control systems, we…"],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-153","name":"Input Data Manipulation"}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2024-09-12T20:22:58.224200Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-47235","exploited":false,"provenance":"source"}}