{"id":"CVE-2024-7847","published":"2024-10-14T13:47:14Z","modified":"2024-10-15T14:05:45Z","title":"RSLogix™ 5 and RSLogix 500® Remote Code Execution Via VBA Embedded Script","vendor":"Rockwell Automation","product":"RSLogix 500®","tier":"tail","description":{"text":"VULNERABILITY DETAILS\n\nRockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. \n\nA feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention.  This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.7,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00185,"percentile":0.08328,"provenance":"source"},"cwes":[{"id":"CWE-345","name":"Insufficient Verification of Data Authenticity"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1701.html","tags":[]}],"priority":{"score":7.1,"factors":[{"name":"EPSS percentile","points":1.67},{"name":"CVSS severity","points":5.39}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"RSLogix 500®","versions":["All"]},{"vendor":"Rockwell Automation","product":"RSLogix™ Micro Developer and Starter","versions":["All"]},{"vendor":"Rockwell Automation","product":"RSLogix™ 5","versions":["All"]}],"workarounds":{"items":["Mitigations and Workarounds Users using the affected software are encouraged to apply the following mitigations and security best practices, where possible. ·       Deny the execution feature in FactoryTalk® Administration Console, when not needed, by navigating to “Policies”, selecting ‘”Enable/Disable VBA”, and then checking the “Deny” box to block VBA code execution. ·       Save project files in a Trusted® location where only administrators can modify it and verify file integrity. ·       Utilize the VBA editor protection feature, which locks the VBA code from viewing and editing by setting a password."],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-19","name":"Embedding Scripts within Scripts"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2024-10-14T15:18:18.670939Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2024-48698","exploited":false,"provenance":"source"}}