{"id":"CVE-2025-0657","published":"2025-11-27T01:00:59Z","modified":"2025-11-28T19:34:27Z","title":"ALC WebCTRL Carrier i-Vu and Gen5 Controllers Array Index out-of-range","vendor":"Automated Logic","product":"WebCtrl","tier":"tail","description":{"text":"A weakness in Automated Logic and Carrier i-Vu Gen5 router on driver\n  version  drv_gen5_106-01-2380, allows\n  malformed packets to be sent through BACnet MS/TP network causing the devices to enter a fault state. This fault state requires a manual power cycle to\n  return the device to network visibility.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.8,"severity":"HIGH","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00358,"percentile":0.30299,"provenance":"source"},"cwes":[{"id":"CWE-129","name":"Improper Validation of Array Index"},{"id":"CWE-248","name":"Uncaught Exception"}],"references":[{"url":"https://www.corporate.carrier.com/product-security/advisories-resources/","tags":[]}],"priority":{"score":12.2,"factors":[{"name":"EPSS percentile","points":6.06},{"name":"CVSS severity","points":6.16}]},"vendorSlug":"automated-logic","affectedVersions":[{"vendor":"Automated Logic","product":"WebCtrl","versions":["<= 8.5"]},{"vendor":"Automated Logic","product":"Gen5 Controllers","versions":["<= drv_gen5_108-04-20120"]},{"vendor":"Carrier","product":"i-Vu","versions":["<= 8.5"]}],"solutions":{"items":["These vulnerabilities have been remediated in cumulative releases for versions 8.5, 9.0, and Gen5 driver version drv_gen5_108-04-20120 or later. Support for versions 8.0, 7.0,6.5, 6.1, 6.0 has expired."],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-11-28T14:41:24.308783Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2025-199779","exploited":false,"provenance":"source"}}