{"id":"CVE-2025-0960","published":"2025-02-04T19:34:25Z","modified":"2025-02-04T19:50:52Z","title":"AutomationDirect C-more EA9 HMI Classic Buffer Overflow","vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T6CL","tier":"tail","description":{"text":"AutomationDirect C-more EA9 HMI contains a function with bounds checks that can be skipped, which could result in an attacker abusing the function to cause a denial-of-service condition or achieving remote code execution on the affected device.","provenance":"source","from":"CVE.org"},"cvss":{"score":9.8,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.01479,"percentile":0.74149,"provenance":"source"},"cwes":[{"id":"CWE-120","name":"Buffer Copy without Checking Size of Input"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-25-035-08","tags":[]},{"url":"https://community.automationdirect.com/s/cybersecurity/security-advisories","tags":[]}],"priority":{"score":21.7,"factors":[{"name":"EPSS percentile","points":14.83},{"name":"CVSS severity","points":6.86}]},"vendorSlug":"automationdirect","affectedVersions":[{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T6CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T7CL-R","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T7CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T8CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T10CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T10WCL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T12CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T15CL-R","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-T15CL","versions":["<= v6.79"]},{"vendor":"AutomationDirect","product":"C-more EA9 HMI EA9-RHMI","versions":["<= v6.79"]}],"solutions":{"items":["AutomationDirect recommends that users update C-MORE EA9 HMI software and firmware to V6.80 https://support.automationdirect.com/firmware/historydetail.php ."],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["If an immediate update is not feasible, AutomationDirect recommends considering the following interim steps until the programming software can be updated: * Isolate the HMI Workstation: Disconnect the HMI from external networks (e.g., internet or corporate LAN) to limit exposure to external threats. * Use dedicated, secure internal networks or air-gapped systems for communication with programmable devices. * Control Access: Restrict physical and logical access to the HMI to authorized personnel only. * Implement Whitelisting: Use application whitelisting to allow only pre-approved and trusted software to execute on the HMI. Block untrusted or unauthorized applications. * Apply Endpoint Security Measures: Use antivirus or endpoint detection and response (EDR) tools to monitor for and mitigate threats. Ensure that host-based firewalls are properly configured to block unauthorized access. * Monitor and Log Activity: Enable logging and monitoring of system activities to detect potential anomalies or unauthorized actions. Regularly review logs for suspicious activity. * Use Secure Backup and Recovery: Regularly back up the workstation and its configurations to a secure location. Test…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2025-02-04T19:50:44.079280Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2025-1945","exploited":false,"provenance":"source"}}