{"id":"CVE-2025-13913","published":"2026-03-12T18:17:22Z","modified":"2026-03-17T15:29:47Z","title":"Inductive Automation Ignition Software Deserialization of Untrusted Data","vendor":"Inductive Automation","product":"Ignition Software","tier":"tail","description":{"text":"A privileged Ignition user, intentionally or otherwise, imports an external file with a specially crafted payload, which executes embedded malicious code.","provenance":"source","from":"CVE.org"},"cvss":{"score":6.3,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:A/AC:H/PR:H/UI:R/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00383,"percentile":0.33224,"provenance":"source"},"cwes":[{"id":"CWE-502","name":"Deserialization of Untrusted Data"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-26-071-06","tags":[]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-071-06.json","tags":[]},{"url":"https://inductiveautomation.com/resources/article/ignition-security-hardening-guide","tags":[]}],"priority":{"score":11.1,"factors":[{"name":"EPSS percentile","points":6.64},{"name":"CVSS severity","points":4.41}]},"vendorSlug":"inductive-automation","affectedVersions":[{"vendor":"Inductive Automation","product":"Ignition Software","versions":["< 8.3.0"]}],"fixedVersions":[{"vendor":"Inductive Automation","product":"Ignition Software","versions":["8.3.0"]}],"solutions":{"items":["Upgrade Ignition software from 8.1.x to 8.3.0 or greater."],"from":"CVE.org CNA","provenance":"source"},"workarounds":{"items":["MITIGATION (8.1.x Linux). Implement Ignition Security Hardening Guide Appendix A. https://inductiveautomation.com/resources/article/ignition-security-hardening-guide","MITIGATION (8.1.x Windows). Covered in Ignition Security Hardening Guide Appendix A. * Create a new dedicated local Windows account that will be used exclusively for the Ignition service (e.g. svc-ign). a. The best security practice is that the Ignition service should not be a domain account (unless otherwise needed). b. Remove all group memberships from the service account (including Users and Administrators). c. Add to security policy to log in as a service. d. Add to \"Deny log on locally\" security policy. * Provide full read/write access only to the Ignition installation directory for the service account created in #1. a. Add read/write permissions to other directories in the local filesystem as needed (e.g.: if configured to use optional Enterprise Administration Module to write automated backups to the file system). * Set deny access settings for service account on other directories not needed by the Ignition service. a. Specifically the C:\\Windows, C:\\Users, and directories for any other applications in the Program Files or Program Files(x86) directories. b. Use java param to change temp directory to a location within the Ignition install directory so the Users folder can…"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2026-03-12T19:06:06.866760Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2025-208615","exploited":false,"provenance":"source"}}