{"id":"CVE-2025-7693","published":"2025-08-18T17:53:08Z","modified":"2025-08-18T18:05:39Z","title":"Rockwell Automation Micro800 Vulnerability","vendor":"Rockwell Automation","product":"PLC - Micro850 L50E","tier":"tail","description":{"text":"A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.","provenance":"source","from":"CVE.org"},"cvss":{"score":9.3,"severity":"CRITICAL","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00416,"percentile":0.36759,"provenance":"source"},"cwes":[{"id":"CWE-20","name":"Improper Input Validation"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1736.html","tags":[]}],"priority":{"score":13.9,"factors":[{"name":"EPSS percentile","points":7.35},{"name":"CVSS severity","points":6.51}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"PLC - Micro850 L50E","versions":["V20.011 - V22.011"]}],"solutions":{"items":["V23.011 and later"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2025-08-18T18:05:26.945400Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2025-25134","exploited":false,"provenance":"source"}}