{"id":"CVE-2025-9177","published":"2025-10-14T12:48:52Z","modified":"2025-10-14T13:36:19Z","title":"Rockwell Automation 1715 EtherNet/IP Comms Module Denial-Of-Service Vulnerability","vendor":"Rockwell Automation","product":"1715-AENTR EtherNet/IP Adapter","tier":"tail","description":{"text":"A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.7,"severity":"HIGH","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00322,"percentile":0.25866,"provenance":"source"},"cwes":[{"id":"CWE-770","name":"Allocation of Resources Without Limits or Throttling"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1757.html","tags":[]}],"priority":{"score":10.6,"factors":[{"name":"EPSS percentile","points":5.17},{"name":"CVSS severity","points":5.39}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"1715-AENTR EtherNet/IP Adapter","versions":["Version 3.003 and prior"]}],"solutions":{"items":["Upgrade to Version 3.011 and later https://compatibility.rockwellautomation.com/Pages/MultiProductFindDownloads.aspx"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2025-10-14T13:36:13.254823Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2025-34192","exploited":false,"provenance":"source"}}