{"id":"CVE-2026-12818","published":"2026-06-30T06:24:11Z","modified":"2026-06-30T12:55:02Z","title":"DVP-12SE Exposure of Sensitive Information Vulnerability","vendor":"deltaww","product":"DVP-12SE","tier":"tail","description":{"text":"Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service.","provenance":"source","from":"CVE.org"},"cvss":{"score":9.3,"severity":"CRITICAL","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00428,"percentile":0.37907,"provenance":"source"},"cwes":[{"id":"CWE-770","name":"Allocation of Resources Without Limits or Throttling"}],"references":[{"url":"https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf","tags":[]}],"priority":{"score":14.1,"factors":[{"name":"EPSS percentile","points":7.58},{"name":"CVSS severity","points":6.51}]},"vendorSlug":"deltaww","workarounds":{"items":["Users are recommended to take the following mitigation measures: * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access. * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with. * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."],"from":"CVE.org CNA","provenance":"source"},"capec":[{"id":"CAPEC-125","name":"Flooding"}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2026-06-30T12:54:54.979527Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-40257","exploited":false,"provenance":"source"}}