{"id":"CVE-2026-17539","published":"2026-09-03T07:59:47Z","modified":"2026-09-03T12:48:06Z","title":"RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a…","vendor":"Hitachi Energy","product":"RTU500 series CMU firmware","tier":"tail","description":{"text":"RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.","provenance":"source","from":"CVE.org"},"cvss":{"score":5.9,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00367,"percentile":0.31302,"provenance":"source"},"cwes":[{"id":"CWE-476","name":"NULL Pointer Dereference"}],"references":[{"url":"https://publisher.hitachienergy.com/preview?DocumentID=8DBD000259&LanguageCode=en&DocumentPartId=&Action=Launch","tags":[]}],"priority":{"score":10.4,"factors":[{"name":"EPSS percentile","points":6.26},{"name":"CVSS severity","points":4.13}]},"vendorSlug":"hitachi-energy","affectedVersions":[{"vendor":"Hitachi Energy","product":"RTU500 series CMU firmware","versions":[">= 12.7.1, <= 12.7.7",">= 13.5.1, <= 13.5.4",">= 13.6.1, <= 13.6.3",">= 13.7.1, <= 13.7.8",">= 13.8.1, <= 13.8.2"]}],"capec":[{"id":"CAPEC-679","name":"Exploitation of Improperly Configured or Implemented Memory Protections"}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2026-09-03T12:47:58.284424Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-70318","exploited":false,"provenance":"source"}}