{"id":"CVE-2026-3611","published":"2026-03-12T20:06:05Z","modified":"2026-03-30T15:26:08Z","title":"Honeywell IQ4x BMS Controller Missing authentication for critical function","vendor":"Honeywell","product":"IQ4E","tier":"tail","description":{"text":"The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.","provenance":"source","from":"CVE.org"},"cvss":{"score":10,"severity":"CRITICAL","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.06298,"percentile":0.93765,"provenance":"source"},"cwes":[{"id":"CWE-306","name":"Missing Authentication for Critical Functionality"}],"references":[{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03","tags":[]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json","tags":[]},{"url":"https://www.honeywell.com/us/en/contact","tags":[]}],"priority":{"score":30.8,"factors":[{"name":"EPSS percentile","points":18.75},{"name":"Public exploit code","points":5.0},{"name":"CVSS severity","points":7.0}]},"exploitSources":{"pocGithub":{"count":1,"skipped":0,"earliest":"2026-08-03","earliestUrl":"https://github.com/spinfosecurity/BAS-Guardian","repos":[{"name":"spinfosecurity/BAS-Guardian","url":"https://github.com/spinfosecurity/BAS-Guardian","stars":1,"created":"2026-08-03"}]},"first":{"date":"2026-08-03","source":"PoC-in-GitHub","url":"https://github.com/spinfosecurity/BAS-Guardian"},"provenance":"source"},"vendorSlug":"honeywell","affectedVersions":[{"vendor":"Honeywell","product":"IQ4E","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQ412","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQ422","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQ4NC","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQ41x","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQ3","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]},{"vendor":"Honeywell","product":"IQECO","versions":[">= v3.50_3.44, <= 4.36 (build 4.3.7.9)"]}],"workarounds":{"items":["Honeywell is aware of the issue, but has not released a fix. For more information, contact Honeywell directly. [https://www.honeywell.com/us/en/contact](https://www.honeywell.com/us/en/contact)."],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"total","timestamp":"2026-03-13T18:02:46.954644Z","from":"CISA ADP","provenance":"source"},"summary":{"text":"The Honeywell IQ4E building management controller exposes its full web-based HMI without authentication in its factory-default configuration, since no user module is configured and the system runs under a System Guest context with read/write privileges. An attacker with network access to the HTTP interface, requiring no credentials or user interaction, can create an administrative account through the pre-authentication user-creation function, which enables authentication under attacker-controlled credentials and can lock legitimate operators out of local and web-based administration.","provenance":"ai","model":"claude-haiku-5-5","generatedAt":"2026-11-21T00:18:05Z"},"euvd":{"id":"EUVD-2026-11706","exploited":false,"provenance":"source"}}