{"id":"CVE-2026-4436","published":"2026-04-09T20:04:26Z","modified":"2026-04-14T14:04:53Z","title":"GPL Odorizers GPL750 Missing Authentication for Critical Function","vendor":"GPL Odorizers","product":"GPL750 (XL4)","tier":"tail","description":{"text":"A low-privileged remote attacker can send Modbus packets to manipulate \nregister values that are inputs to the odorant injection logic such that\n too much or too little odorant is injected into a gas line.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.6,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00456,"percentile":0.40471,"provenance":"source"},"cwes":[{"id":"CWE-306","name":"Missing Authentication for Critical Functionality"}],"references":[{"url":"https://lincenergysystems-my.sharepoint.com/:f:/p/h_baer/IgDYaHIhXpyLQJvnKPd6b80TAUgV7Lp8qmVYBFUb0lmr7ak?e=JLeADm","tags":[]},{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-26-099-02","tags":[]},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-099-02.json","tags":[]}],"priority":{"score":14.1,"factors":[{"name":"EPSS percentile","points":8.09},{"name":"CVSS severity","points":6.02}]},"vendorSlug":"gpl-odorizers","affectedVersions":[{"vendor":"GPL Odorizers","product":"GPL750 (XL4)","versions":[">= v1.0, < v6.0"]},{"vendor":"GPL Odorizers","product":"GPL750 (XL4 Prime)","versions":[">= v4.0, < v6.0"]},{"vendor":"GPL Odorizers","product":"GPL Odorizers GPL750 (XL7)","versions":[">= v13.0, < v20.0"]},{"vendor":"GPL Odorizers","product":"GPL Odorizers GPL750 (XL7 Prime)","versions":[">= v18.4, < v20.0"]}],"solutions":{"items":["GPL Odorizers recommends users update to the latest software version of the GPL750 in connection with the latest firmware from Horner Automation for the XL4, XL4 Prime, XL7, and XL7 Prime devices.https://lincenergysystems-my.sharepoint.com/:f:/p/h_baer/IgDYaHIhXpyLQJvnKPd6b80TAUgV7Lp8qmVYBFUb0lmr7ak?e=JLeADm. https://lincenergysystems-my.sharepoint.com/:f:/p/h_baer/IgDYaHIhXpyLQJvnKPd6b80TAUgV7Lp8qmVYBFUb0lmr7ak?e=JLeADm","GPL Odorizers recommends users clear the old files from their microSD cards, keeping only the LOGS folder and the FIRMWARE.LIC file if they have a WebMI license. The compressed folder downloaded from the link above can then be extracted to the root directory of the microSD card. These files already include the corresponding firmware update. If users do not have IT permissions to access their microSD cards, GPL Odorizers can provide preconfigured SD cards that technicians can simply swap into their odorizers prior to installation.","For assistance in updating GPL Odorizers to the latest version, users should reach out to GPL Odorizers directly via phone number (303) 697-6701 during the hours of 8:00 a.m. to 4:00 p.m. MST.","Horner Automation offers firmware version 15.76 for their XL Series and version 17.30 for their XL Prime Series controllers. An installation guide is available for both the XL series and the XL Prime series. https://hornerautomation.com/controller-firmware/"],"from":"CVE.org CNA","provenance":"source"},"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2026-04-14T14:03:00.899159Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-21066","exploited":false,"provenance":"source"}}