{"id":"CVE-2026-47711","published":"2026-11-12T20:05:20Z","modified":"2026-11-13T00:31:30Z","title":"BACnet Stack: Stack buffer overflow in Loop internal ReadProperty path via Life_Safety_Zone.accepted-modes on the…","vendor":"bacnet-stack","product":"bacnet-stack","tier":"tail","description":{"text":"BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4, 1.5.1, and 1.6.0, the current master demo server can be crashed remotely over BACnet/IP by sending a valid Confirmed WriteProperty request that updates loop-1's controlled-variable-reference to point to life-safety-zone-1 / accepted-modes. This issue has been patched in versions 1.4.4, 1.5.1, and 1.6.0.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.6,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00282,"percentile":0.21219,"provenance":"source"},"cwes":[{"id":"CWE-121","name":"Stack-based Buffer Overflow"},{"id":"CWE-131","name":"Incorrect Calculation of Buffer Size"},{"id":"CWE-787","name":"Out-of-bounds Write"},{"id":"CWE-805","name":"Buffer Access with Incorrect Length Value"}],"references":[{"url":"https://github.com/bacnet-stack/bacnet-stack/security/advisories/GHSA-vrpm-9gm2-x552","tags":["x_refsource_CONFIRM"]}],"priority":{"score":10.3,"factors":[{"name":"EPSS percentile","points":4.24},{"name":"CVSS severity","points":6.02}]},"vendorSlug":"bacnet-stack","affectedVersions":[{"vendor":"bacnet-stack","product":"bacnet-stack","versions":["< 1.4.4","< 1.5.1","< 1.6.0"]}],"ssvc":{"exploitation":"none","automatable":"yes","technicalImpact":"partial","timestamp":"2026-11-13T00:31:09.971913Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-124672","exploited":false,"provenance":"source"}}