{"id":"CVE-2026-62973","published":"2026-11-13T15:59:09Z","modified":"2026-11-13T21:08:56Z","title":"BACnet Stack: Remote Global-Buffer-Overflow Read in readpropm via Malformed ReadPropertyMultiple-ACK","vendor":"bacnet-stack","product":"bacnet-stack","tier":"tail","description":{"text":"BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.5, 1.5.1, and 1.6.0, a remote out-of-bounds read exists in the official BACnet client application apps/readpropm in bacnet-stack commit e2bdbf6. When readpropm sends a legitimate ReadPropertyMultiple request to a malicious BACnet/IP peer, the peer can reply with a malformed but structurally valid ReadPropertyMultiple-ACK that drives the client into a global-buffer-overflow read on the global receive buffer Rx_Buf. This issue has been patched in versions 1.4.5, 1.5.1, and 1.6.0.","provenance":"source","from":"CVE.org"},"cvss":{"score":7.5,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00428,"percentile":0.37961,"provenance":"source"},"cwes":[{"id":"CWE-125","name":"Out-of-bounds Read"}],"references":[{"url":"https://github.com/bacnet-stack/bacnet-stack/security/advisories/GHSA-3xxw-jfwm-rq9c","tags":["x_refsource_CONFIRM"]},{"url":"https://github.com/bacnet-stack/bacnet-stack/pull/1395","tags":["x_refsource_MISC"]}],"priority":{"score":12.8,"factors":[{"name":"EPSS percentile","points":7.59},{"name":"CVSS severity","points":5.25}]},"vendorSlug":"bacnet-stack","affectedVersions":[{"vendor":"bacnet-stack","product":"bacnet-stack","versions":["< 1.4.5","< 1.5.1","< 1.6.0"]}],"ssvc":{"exploitation":"poc","automatable":"yes","technicalImpact":"partial","timestamp":"2026-11-13T21:08:38.040564Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-125540","exploited":false,"provenance":"source"}}