{"id":"CVE-2026-63352","published":"2026-10-13T09:18:36Z","modified":"2026-10-14T13:44:30Z","title":"Affected devices do not properly sanitize calculated signal data contained in imported CSV trace files before…","vendor":"Siemens","product":"SIMATIC Drive Controller CPU 1504D TF","tier":"tail","description":{"text":"Affected devices do not properly sanitize calculated signal data contained in imported CSV trace files before rendering it on the Trace page.\r\n\r\nThis could allow an attacker to social engineer an authorized user who holds the function right “Read diagnostics” into importing a specially crafted trace file. Successful exploitation could allow attacker-controlled JavaScript to execute in the user’s browser session and perform PLC operations through the web server within the scope of the user’s authorization.","provenance":"source","from":"CVE.org"},"cvss":{"score":6.1,"severity":"MEDIUM","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00253,"percentile":0.10243,"provenance":"source"},"cwes":[{"id":"CWE-79","name":"Improper Neutralization of Input During Web Page Generation"}],"references":[{"url":"https://cert-portal.siemens.com/productcert/html/ssa-591731.html","tags":[]}],"priority":{"score":6.3,"factors":[{"name":"EPSS percentile","points":2.05},{"name":"CVSS severity","points":4.27}]},"vendorSlug":"siemens","affectedVersions":[{"vendor":"Siemens","product":"SIMATIC Drive Controller CPU 1504D TF","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC Drive Controller CPU 1507D TF","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1510SP F-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1510SP F-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1510SP-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1510SP-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1512SP F-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1512SP F-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1512SP-1 PN","versions":["all versions"]},{"vendor":"Siemens","product":"SIMATIC ET 200SP CPU 1512SP-1 PN","versions":["all versions"]}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"partial","timestamp":"2026-10-14T13:44:16.397310Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-98383","exploited":false,"provenance":"source"}}