{"id":"CVE-2026-84860","published":"2026-09-16T14:52:23Z","modified":"2026-09-17T18:37:14Z","title":"Scada-LTS DWR Authorization Bypass - Systemic","vendor":"Scada-LTS","product":"Scada-LTS","tier":"tail","description":{"text":"ScadaLTS 2.8.1-release-candidate build 0 is affected by an Authorization Bypass\n\n\n\nSpring Security gates DWR endpoints by URL path pattern, but DWR itself dispatches method calls based on the POST body parameters c0-scriptName and c0-methodName. The crossDomainSessionSecurity setting in web.xml is set to false, which disables DWR's built-in origin validation. This means any authenticated user can invoke any DWR method (regardless of the URL-based access control) by sending their request to a URL they are permitted to access (e.g. MiscDwr.initializeLongPoll.dwr) while targeting a restricted class in the POST body.\n\n\n\nThis is the systemic root cause that enables multiple other findings to be exploited as a low privilege user.","provenance":"source","from":"CVE.org"},"cvss":{"score":8.8,"severity":"HIGH","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00482,"percentile":0.34016,"provenance":"source"},"cwes":[{"id":"CWE-639","name":"Authorization Bypass Through User-Controlled Key"}],"references":[{"url":"https://www.tenable.com/security/research/tra-2026-60","tags":[]}],"priority":{"score":13.0,"factors":[{"name":"EPSS percentile","points":6.8},{"name":"CVSS severity","points":6.16}]},"vendorSlug":"scada-lts","affectedVersions":[{"vendor":"Scada-LTS","product":"Scada-LTS","versions":["2.8.1"]}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2026-09-17T18:36:47.898521Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-80827","exploited":false,"provenance":"source"}}