{"id":"CVE-2026-9633","published":"2026-09-01T13:45:15Z","modified":"2026-09-01T15:49:43Z","title":"Redundancy Module Configuration Tool - Multiple Vulnerabilities","vendor":"Rockwell Automation","product":"Redundancy Module Configuration Tool","tier":"tail","description":{"text":"A security issue exists within the Redundancy Module Configuration Tool. The RM3ConfigTool.exe binary searches directories in the system path for a required DLL, and one or more of these directories may be writable by standard (non-administrator) users due to incorrect default permissions. If a local attacker places a malicious DLL in such a directory and an administrator subsequently runs the tool, the malicious DLL is loaded into the elevated process and executes with Administrator/SYSTEM privileges.","provenance":"source","from":"CVE.org"},"cvss":{"score":7,"severity":"HIGH","version":"4.0","vector":"CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N","provenance":"source","from":"CVE.org CNA"},"epss":{"score":0.00131,"percentile":0.02771,"provenance":"source"},"cwes":[{"id":"CWE-276","name":"Incorrect Default Permissions"}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1800.html","tags":[]}],"priority":{"score":5.5,"factors":[{"name":"EPSS percentile","points":0.55},{"name":"CVSS severity","points":4.9}]},"vendorSlug":"rockwell-automation","affectedVersions":[{"vendor":"Rockwell Automation","product":"Redundancy Module Configuration Tool","versions":["10.00.00"]}],"ssvc":{"exploitation":"none","automatable":"no","technicalImpact":"total","timestamp":"2026-09-01T15:49:35.846936Z","from":"CISA ADP","provenance":"source"},"euvd":{"id":"EUVD-2026-69147","exploited":false,"provenance":"source"}}