Patchfirst
CVE-2014-0750 Public exploit High · 7.5 EPSS 69.8%

GE Proficy HMI/SCADA Path Traversal

Fix:see the vendor's fix instructions Instructions ↓

GE · Proficy HMI/SCADA - CIMPLICITY

Official description · CVE.org

Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.

Breakdown
30.1 / 100
Exploited
Not confirmed
Reports
0
Tactics
0/15

Public exploit code (Metasploit) was available 2 days before disclosure.

  1. Public exploit codeMetasploit2 days before
  2. Disclosedday 0

Affected versions and fixes

as published in the CVE record

GE Proficy HMI/SCADA - CIMPLICITY

Affected: >= 4.01, < 8.2

GE Proficy Process Systems with CIMPLICITY

Affected: all versions

Fix

GE has produced an update that mitigates one vulnerability and made configuration changes to mitigate the other. Please reference the following GE Product Security Advisories for specific information on the vulnerabilities. GEIP13-05 To address this vulnerability, all copies of the gefebt.exe files that are accessible from a Web client must be deleted or moved, so they are inaccessible. If the production Web configuration currently relies on gefebt.exe, changes to the server’s Web pages may also be desirable. The GE Product Security Advisory, which provides additional guidance, is available here:  http://support.ge-ip.com/support/index?page=kbchannel&id=KB15939 GEIP13-06 Download Proficy HMI/SCADA - CIMPLICITY 8.2 SIM 24 at:  http://support.ge-ip.com/support/index?page=dwchannel&id=DN4128 The GE Product Security Advisory is available here:  http://support.ge-ip.com/support/index?page=kbchannel&id=KB15940

References

4 links, grouped by NVD tag
↑ ↓ chooseEnter openEsc close