GE Proficy HMI/SCADA Path Traversal
Fix:see the vendor's fix instructions Instructions ↓
GE · Proficy HMI/SCADA - CIMPLICITY
Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.
- Exploited
- Not confirmed
- Reports
- 0
- Tactics
- 0/15
Exploitation timelineDated milestones for a CVE: when it was disclosed, when exploit code became public, when exploitation was confirmed, and when threat reports named it.
Public exploit code (Metasploit) was available 2 days before disclosure.
- Public exploit codeMetasploit2 days before
- Disclosedday 0
Affected versions and fixes
as published in the CVE recordGE Proficy HMI/SCADA - CIMPLICITY
Affected: >= 4.01, < 8.2
GE Proficy Process Systems with CIMPLICITY
Affected: all versions
Fix
GE has produced an update that mitigates one vulnerability and made configuration changes to mitigate the other. Please reference the following GE Product Security Advisories for specific information on the vulnerabilities. GEIP13-05 To address this vulnerability, all copies of the gefebt.exe files that are accessible from a Web client must be deleted or moved, so they are inaccessible. If the production Web configuration currently relies on gefebt.exe, changes to the server’s Web pages may also be desirable. The GE Product Security Advisory, which provides additional guidance, is available here: http://support.ge-ip.com/support/index?page=kbchannel&id=KB15939 GEIP13-06 Download Proficy HMI/SCADA - CIMPLICITY 8.2 SIM 24 at: http://support.ge-ip.com/support/index?page=dwchannel&id=DN4128 The GE Product Security Advisory is available here: http://support.ge-ip.com/support/index?page=kbchannel&id=KB15940