GE Proficy HMI/SCADA Path Traversal
Fix:see the vendor's fix instructions Instructions ↓
GE · Proficy HMI/SCADA - CIMPLICITY
The CIMPLICITY Web-based access component, CimWebServer, does not check the location of shell files being loaded into the system. By modifying the source location, an attacker could send shell code to the CimWebServer which would deploy the nefarious files as part of any SCADA project. This could allow the attacker to execute arbitrary code.
- Exploited
- Yes, in VulnCheck KEV
- Reports
- 0
- Tactics
- 0/15
Exploitation timelineDated milestones for a CVE: when it was disclosed, when exploit code became public, when exploitation was confirmed, and when threat reports named it.
First seen exploited 10 months after disclosure.
- Disclosedday 0
- First seen exploitedVulnCheck KEV evidence+10 mo
MITRE ATT&CKA public catalogue of the techniques attackers use, maintained by MITRE. Patchfirst uses it to describe what attackers do with a vulnerability. techniques
No techniques linkedNo high- or medium-confidence techniques. The 7 available links are lower confidence and listed below.
Lower-confidence links (7)
These come from early or generic mappings, text matching, or contradict this CVE’s details (for example a public-facing technique on a bug that needs a user to open a file). Shown for completeness.
- Data from Local SystemT1005 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- External Remote ServicesT1133 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- Exploit Public-Facing ApplicationT1190 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- Exploitation of Remote ServicesT1210 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- Exploitation for StealthT1211 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- Exploitation for Credential AccessT1212 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
- Unsecured CredentialsT1552 CTID attack_to_cve Phase 1 "Uncategorized" mapping (not staged by impact)
Affected versions and fixes
as published in the CVE recordGE Proficy HMI/SCADA - CIMPLICITY
Affected: >= 4.01, < 8.2
GE Proficy Process Systems with CIMPLICITY
Affected: all versions
Fix
GE has produced an update that mitigates one vulnerability and made configuration changes to mitigate the other. Please reference the following GE Product Security Advisories for specific information on the vulnerabilities. GEIP13-05 To address this vulnerability, all copies of the gefebt.exe files that are accessible from a Web client must be deleted or moved, so they are inaccessible. If the production Web configuration currently relies on gefebt.exe, changes to the server’s Web pages may also be desirable. The GE Product Security Advisory, which provides additional guidance, is available here: http://support.ge-ip.com/support/index?page=kbchannel&id=KB15939 GEIP13-06 Download Proficy HMI/SCADA - CIMPLICITY 8.2 SIM 24 at: http://support.ge-ip.com/support/index?page=dwchannel&id=DN4128 The GE Product Security Advisory is available here: http://support.ge-ip.com/support/index?page=kbchannel&id=KB15940
What security researchers reported
Not named in any threat report yetAlso mentioned in 1 community threat pulse (AlienVault OTX)
Weaker evidencePulses are indicator collections that anyone can publish. A mention is not confirmation of exploitation.
- 2015: Malware Analysis Report1 May 2026