CVE-2023-3595 Critical · 9.8 EPSS 5.5%

Rockwell Automation ControlLogix Communication Modules Vulnerable to Remote Code Execution

Fix:see the vendor's fix instructions Instructions ↓

Rockwell Automation · 1756-EN2T Series A, B, C

Summary

The flaw is an out-of-bounds write in the communication modules of Rockwell Automation's ControlLogix line, specifically the 1756-EN2T Series A, B and C products. An attacker who sends maliciously crafted CIP messages to an affected module can achieve remote code execution with persistence, and can modify, deny or exfiltrate data passing through the device, with no authentication or user interaction required and only network access needed to reach it.

Official description · CVE.org

Where this vulnerability exists in the Rockwell Automation 1756 EN2* and 1756 EN3* ControlLogix communication products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device.

Breakdown
60.5 / 100
Exploited
Yes, in VulnCheck KEV
Reports
0
Tactics
0/15

First seen exploited 7 months after disclosure.

  1. Disclosedday 0
  2. First seen exploitedVulnCheck KEV evidence+7 mo

Affected versions and fixes

as published in the CVE record

Rockwell Automation 1756-EN2T Series A, B, C

Affected: <=5.008 & 5.028

Rockwell Automation 1756-EN2T Series D

Affected: <=11.003

Rockwell Automation 1756-EN2TK Series A, B, C

Affected: <=5.008 & 5.028

Rockwell Automation 1756-EN2TXT Series A, B, C

Affected: <=5.008 & 5.028

Rockwell Automation 1756-EN2TXT Series D

Affected: <=11.003

Rockwell Automation 1756-EN2TP Series A

Affected: <=11.003

Rockwell Automation 1756-EN2TPK Series A

Affected: <=11.003

Rockwell Auotmation 1756-EN2TPXT Series A

Affected: <=11.003

Rockwell Automation 1756-EN2TR Series A, B

Affected: <=5.008 & 5.028

Rockwell Automation 1756-EN2TR Series C

Affected: <=11.003

Fix

* Update firmware. Update EN2* ControlLogix communications modules to mitigated firmware. * Properly segment networks. Given a cyber actor would require network connectivity to the communication module to exploit the vulnerability, organizations should ensure ICS/SCADA networks are properly segmented within the process structure as well as from the Internet and other non-essential networks. * Implement detection signatures. Use appended Snort signatures to monitor and detect anomalous Common Industrial Protocol (CIP) packets to Rockwell Automation devices.

Attack pattern (CAPEC)

CAPEC-100 Overflow Buffers

References