Rockwell Automation ControlLogix Communication Modules Vulnerable to Remote Code Execution
Fix:see the vendor's fix instructions Instructions ↓
Rockwell Automation · 1756-EN2T Series A, B, C
The flaw is an out-of-bounds write in the communication modules of Rockwell Automation's ControlLogix line, specifically the 1756-EN2T Series A, B and C products. An attacker who sends maliciously crafted CIP messages to an affected module can achieve remote code execution with persistence, and can modify, deny or exfiltrate data passing through the device, with no authentication or user interaction required and only network access needed to reach it.
Official description · CVE.org
Where this vulnerability exists in the Rockwell Automation 1756 EN2* and 1756 EN3* ControlLogix communication products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device.
- Exploited
- Yes, in VulnCheck KEV
- Reports
- 0
- Tactics
- 0/15
Exploitation timelineDated milestones for a CVE: when it was disclosed, when exploit code became public, when exploitation was confirmed, and when threat reports named it.
First seen exploited 7 months after disclosure.
- Disclosedday 0
- First seen exploitedVulnCheck KEV evidence+7 mo
Affected versions and fixes
as published in the CVE recordRockwell Automation 1756-EN2T Series A, B, C
Affected: <=5.008 & 5.028
Rockwell Automation 1756-EN2T Series D
Affected: <=11.003
Rockwell Automation 1756-EN2TK Series A, B, C
Affected: <=5.008 & 5.028
Rockwell Automation 1756-EN2TXT Series A, B, C
Affected: <=5.008 & 5.028
Rockwell Automation 1756-EN2TXT Series D
Affected: <=11.003
Rockwell Automation 1756-EN2TP Series A
Affected: <=11.003
Rockwell Automation 1756-EN2TPK Series A
Affected: <=11.003
Rockwell Auotmation 1756-EN2TPXT Series A
Affected: <=11.003
Rockwell Automation 1756-EN2TR Series A, B
Affected: <=5.008 & 5.028
Rockwell Automation 1756-EN2TR Series C
Affected: <=11.003
Fix
* Update firmware. Update EN2* ControlLogix communications modules to mitigated firmware. * Properly segment networks. Given a cyber actor would require network connectivity to the communication module to exploit the vulnerability, organizations should ensure ICS/SCADA networks are properly segmented within the process structure as well as from the Internet and other non-essential networks. * Implement detection signatures. Use appended Snort signatures to monitor and detect anomalous Common Industrial Protocol (CIP) packets to Rockwell Automation devices.
Attack pattern (CAPEC)
CAPEC-100 Overflow Buffers